Tender No. MRTS/SC-593/15(ISS)/Pt.I, dtd. 25.05.2010
“ In continuation to the earlier corrigenda regarding Tender No. MRTS/SC-593/15(ISS)/Pt.I, published on 11.02.2010, 18.02.2010, 19.03.2010, 11.04.2010, 30.04.2010, 09.05.2010 & 19.05.2010, following is notified to all concerned.
1. Ann-S&T/Amend/4, now included under the head Technical Parameters, shall be part of the above Open Tender .

2. Sl. No. 5 under the heading A. Provision of Security items : of Annexure-B (Schedule of Items) & Annexure-C (Schedule of Rates) to be read as “ Bomb Suppression Blanket & Bomb Basket ” instead of “Bomb Suppression Blanket/Bomb Basket” and quantity should be read 25 + 25 i.e. both the items to be treated as separate item within the same base value of Rs. 25,00,000/- (consolidated) for the items.
Tenderers may quote their rate keeping in mind that both the items to be supplied 25 + 25 (Bomb Suppression Blanket & Bomb Basket).

3. Clarification to the queries raised by different firms in connection with the above Open Tender shall also be available in the websites.

4. The addendum at Item 1, the corrigendum at Item 2 and the clarification at Item 3 above shall be available in the websites viz. www.kolmetro.com and/or www.indianrailways.gov.in, from 25.05.2010 onwards.
All other terms & conditions spelt out in the tender shall stand good.”
 
Sub : S&T's clarification on the bidders' queries

A) Query of M/s bclsecurepremises vide their letter No.BCL/ESS/KOLMET/001/2010 dtd.06.05.2010

Q/No.
Query
Metro Railway's Clarification
1
In the revised tender document in Annexure C. Schedule of rates, B-CCTV Items Point 14 “raid 5 based storage Device Qty 2 as per KOL Metro BOQ sheet (page- 69).While as per RDSO Specification Sheet Sr. No. 5.11.4 (page-23 of 48) says “The system should provide minimum 18.0 TB usable after RAID 5 configurations for every 32 cameras for storing minimum 30 days recording or as specified by Purchaser” . As per RDSO clause the total quantity of storage will go to 23 + (one Storage per station as every station have around 30 – 32 cameras)

Two nos. of SAN/NAS of size 10 TB usable each against item no.14 of Schedule-B in Annexure-C will be used in OCC for storing of sensitive videos from selected cameras for analysis etc. Although RDSO specification does not include NAS specification, the bidder can offer NAS of reputed make for consideration. The station level recording of nearly 30 cameras will be made in the Storage Server, for which 4 TB HDD has been specified. Metro railway is well aware of the limitation of the storage space under the scope of the present tender and hence it will have to be satisfied with a recording of minimum seven days at station level. There is no such duration stipulation for central storage, as it will depend on strategic selection of cameras on a day-to-day basis.

2
Revised tender Document asks cost for 24 port layer 2 switches qty 60 and 2 nos. layer 3 (page – 68), while RDSO specification sheet Sr. No. 5.12 (page – 23 of 48) asks 8 port layer 2 switches and 24 port layer 3 switch (Sr.No.5.13 of page – 23 of 48). If we quote as per RDSO doc quantity will differ and design will also get change.
Metro Railway has given specification of both station level and core switches separately under Technical Parameters and hence RDSO specification will not be applicable for the switches.
3,4,5&6  
Not linked with S&T department
 
B) Query of M/s Bharat Electronics Ltd. vide their letter no.20514/16/575/Mktg/NAMU dtd. 20.04.2010
Q/No. Item Description/Page No./Item No. Query/Suggestion Metro Railway's Clarification
1

High Resolution MPEG-4 and MJPEG compression based etc.Page62/Item No.1

We suggest you to follow latest RDSO specs SPN/TC/65/2006 Rev 1.0 since currently available products comply with these latest specs.

Suggested changes are already incorporated vide Clause No.30 of Technical Parameters. Railway Board's Specification given earlier in TD from Page No.71 to 118 stands deleted. BOQ is being amended suitably to avoid confusion.
(vide Amendment/Corrigendum that follows)

2

High Resolution MPEG-4 and MJPEG compression based etc.Page62/Item No.2

H.264 is the upgraded tech. Version of MPEG 4. We suggest you to follow latest RDSO specs SPN/TC/65/2006 Rev 1.0 since currently available products comply with these latest specs

………..DO…………
3

MPEG-4 Encoder with Analytic support Page63/Item No.4

…………DO………..

Suggested changes are already incorporated vide Clause No.30 of Technical Parameters. Railway Board's Specification given earlier in TD from Page No.71 to 118 stands deleted.
(vide Amendment/Corrigendum that follows)

4

Server Page63/Item No.6

………..NIL………….
………..NIL………….
5

Server Page63/Item No.5

………..NIL………….
………..NIL………….
6

Video Management/ Recording/ Analytics Software Page-63/Item No.7

H.264 is the upgraded tech. Version of MPEG 4. We suggest you to follow latest RDSO specs SPN/TC/65/2006 Rev 1.0 since currently available products comply with these latest specs

Suggested changes are already incorporated vide Clause No.30 of Technical Parameters. Railway Board's Specification given earlier in TD from Page No.71 to 118 stands deleted. (vide Amendment/Corrigendum that follows)

7

Video Management/ Recording/Analytics Software Page-63/Item No.7

……….DO…………..
……….DO…………..
8

RAID 5 Based Storage Device for storing recorded video Page-63/Item No.14

We suggest you to follow latest RDSO specs SPN/ TC/65/2006 Rev 1.0 since currently available products comply with these latest spec

Latest RDSO specification is being followed. However, usable storage has been limited to 10 TB in place of 18 TB as in RDSO specification. Also, it has been mentioned that NAS will be preferred to SAN.
9
Work Station for Network Management & Monitoring
………….DO…………
Suggested changes are already incorporated.
10

We suggest you to follow Latest RDSO specs SPN/TC/65/2006 Rev 1.0 Since currently available products comply with these latest specs

UPS specification is also in suggested line vide Clause No.24 of Technical Parameters. But, UPS against Item No.15 will be of higher capacity, namely 2 hr backup, as mentioned in the description of material in the Schedule of Rates(Annexure-C). All other parameters of this UPS also will be as per RDSO specification no.SPN/TC/65/2006 Rev 1.0

 
C) Query of M/s TERACOM LTD. vide their letter no.TL/KM/ISS/2010/05/006 dtd.06.05.2010
Q/No. Clause No. Query Metro Railway's Clarification
1
Page-63, S.No.5

We understand that there are 23 locations of Metro Stations then as per the SOR Railways have asked for 30 servers .Please clarify.

There are 23 stations, but 30 locations vide location break-up given in Clause No.8 of Technical Parameters
2
Page-63, S.No.6

We understand that there are 23 locations of Metro Stations then as per SOR Railways have asked for 30 servers. Please clarify.

23 nos. storage servers will be used in 23 stations. The remaining 7 nos. will be used in Metro Bhavan in conjunction with NAS/SAN of 20 TB usable capacity as central storage.
3
Page-63, S.No.6

We assume servers mentioned in Sr. No.6 are For VMS and video analytics requirement.But Apart from them there should be client Workstations on each station for connection Display monitors which are missing from the BOQ please clarify.
Please note that in CCTV it is recommended To have separate workstations for monitoring Servers should not be used for video display Even RDSO recommended the same.

The bidder will be required to quote Workstations as per RDSO Specification no.SPN/TC/65/2006 Rev 1.0 against Item No.23 of Part.B of Schedule of Rates(Annexure-C). BOQ is being suitably revised.(vide Amendment/Corrigendum that follows)
4
Page-63, S.No.7

All the cameras will be recorded at their respective stations. With each station having 30 camera. Then what is the purpose of asking for another set of 763 recording and analytics Licenses? If it is intended to record all the Cameras parallel in central place also than you need 30 servers on central location as well. Please clarify.

The composite video signal coming from all the stations will be viewed and monitored at 5 locations, where it may be required to archive and analyze video signals also. Hence, the license for 763 cameras for five user. All the cameras may not be required to be recorded for all the time at OCC. For this, five to seven servers may be sufficient. If not, the bidder is free to bid for additional servers against Item No.23 of Part.-B of Schedule of Rates(Annexure-C)

5
Page-63, S.No.12
How many ports should be there to convert Ethernet to Fiber Ports and vice versa.
Exact number cannot be indicated. The bidder may at his convenience do the field level assessment before bidding, for which Metro Railway is always ready to cooperate.
6 Page-63, S.No.18 Please provide the details regarding Doors, fans and PDU.

The rack specification is as under: -
19 inch Server Rack 42U 600mm(W)X1000mm(D)X2013mm(H) with robust structure and industrial design to take the load of minimum two servers and 4 nos. Switches apart from other minor network equipment. The rack preferably of black finish should have the following:-
a)Front vent glass door- 01 no. b)Mesh back door- 01 no.
c) Side panels with ventilation & slam latch-02 nos.
d)Casters with brake to withstand a minimum of 650 kgs -04 nos.
e)A/C mains Vertical with 12 nos. of 5A socket-01no.
f)Front panel mounting hardware-02 nos.
g)230V AC 90 cfm fan mounted on to cover –04 nos.
h)H/D Stationary Shelf-700mm depth-01 no.
i)19 inch Keyboard Tray-02 nos. (vide Amendment/Corrigendum that follows))

7
Page-63, S.No.21
There are 5 workstations, whether these need to be deployed ? On stations or at Metro Bhavan.
These will be required for viewing and monitoring at MRP/ESP, RPF/TOL, RPF/DMI, RPF/NGA & RPF/MB

8 to
10

 

 

Not related to S&T department
11
Page-121, Clause-30
RDSO Specification Clause Nos.5.6, 5.12 & 5.13 for large display unit, Layer-2 Switch and Layer-3 Switch are not applicable and stand superseded by the specification given against Clause-No.9, 10, 14 & 16 of Technical Parameters
 
D) Amendments
Item No. Of Relevant Part of text / figure To be amended as
1
Part-B of Annexure-B(Page-62)
High Resolution MPEG-4 & MJPEG Compression based Day & Night IP Camera complete with lens assembly, CCD,IR filter, POE switch, Power Supply, housing, mounting arrangement etc. suitable for gates, tunnel, escalators, platforms, concourse, yards & ventilation points.
High Resolution Day & Night IP Camera complete with lens assembly, CCD,IR filter, POE switch, Power supply, housing, mounting arrangement etc. suitable for gates, tunnel, escalators, platforms, concourse, yards & ventilation points (As per RDSO Specification No. SPN/TC/65/2006 Rev 1.0)
2
Part-B of Annexure-B(Page-62 & 63)
High Resolution MPEG-4 & MJPEG Compression based Day & Night IP PTZ Camera complete with lens assembly, CDD,POE switch, Power Supply, housing & mounting arrangement etc. suitable for lobby, carsheds,'Y' & ‘X' sidings and other strategic points.
High Resolution Day & Night IP PTZ Camera complete with lens assembly, CCD,POE switch, Power Supply housing & mounting arrangement etc. suitable for lobby, carsheds, ‘Y' & ‘X' sidings and other strategic point (As per RDSO Specification No. SPN/TC/65/2006 Rev 1.0)
11
Part-B of Annexure-B(Page-63)
42?-50? TFT Panel/Monitors
42 inch-50 inch TFT Pane/Monitors (As per Metro Rly's specification at Ann-S&T/Amend/2)
18
Part-B of Annexure-B(Page-63)
19” Rack (42U) (Make:Valrack/IBM/HP/APW President)
19” Rack(42U) as per Metro Rly's specification at Ann-S&T/Amend/4 (Make:Valrack/IBM/HP/APW President)
21
Part-B of Annexure-B(Page-64)
5
30
1
Part-B of Annexure-C(Page-66)
High Resolution MPEG-4 & MJPEG Compression based Day & Night IP Camera complete with lens assembly, CCD, IR filter, POE switch, Power Supply, housing, mounting arrangement etc. suitable for gates, tunnel, escalators, platforms, concourse, yards & ventilation points

High Resolution Day & Night IP Camera complete with lens assembly, CCD, IR filter, POE switch, Power Supply, housing, mounting arrangement etc. suitable for gates, tunnel, escalators, platforms, concourse, yards & ventilation points (As per RDSO Specification No. SPN/TC/65/2006 Rev 1.0)

2
Part-B of Annexure-C(Page-66)
High Resolution MPEG-4 & MJPEG Compression based Day & Night IP PTZ Camera complete with lens assembly, CCD, POE switch, Power Supply, housing & mounting arrangement etc. suitable for lobby, carsheds, ‘Y' & ‘X' sidings and other strategic points
High Resolution Day & Night IP PTZ Camera complete with lens assembly, CCD,POE switch, Power Supply, housing & mounting arrangement etc. suitable for lobby, carsheds, ‘Y' & ‘X' sidings and other strategic points (As per RDSO Specification No. SPN/TC/65/2006 Rev 1.0)
11
Part-B of Annexure-C(Page-68)
42?-50? TFT Panel/Monitors
42 inch-50 inch TFT Panel/Monitors (As per Metro Rly's specification at Ann-S&T/Amend/2)
18
Part-B of Annexure-C(Page-70)
19” Rack (42U) (Make: Valrack/IBM/HP/APW/President)
19” Rack (42U) as per Metro Rly's specification at Ann-S&T/Amend/4 (Make:Valrack/IBM/HP/APW President)
21
Part-B of Annexure-C(Page-70)
625000
3750000
 
E) Addendum to Technical Parameters (Page-119 to 121)
31. Railway Board's Specification given as Annexure-D in the tender document from Page No. 71 to 118 stands deleted.
Ann-S&T/Amend/4
Specification of 19 inch Rack (42U)
The rack specification is as under :-
19 inch Server Rack 42U 600mm (W)X1000mm(D)X2013mm(H) with robust structure and industrial design to take the load of minimum two servers and 4 nos. Switches apart from other minor network equipment. The rack preferably of black finish should have the following: -
a) Front vent glass door – 01 no.
b) Mesh back door-01 no.
c) Side panels with ventilation & slam latch-02 nos.
d) Casters with brake to withstand a minimum of 650 kgs-04 nos.
e) A/C mains Vertical with 12 nos. of 5A socket-01no.
f) Front panel mounting hardware –02 nos.
g) 230V AC 90 cfm fan mounted on to cover –04 nos.
h) H/D Stationary Shelf-700mm depth-01 no.
i) 19 inch Keyboard Tray-02 nos.
 
Chief Operations Manager